SIVACOII 8PT drawer type low voltage switch cabinet

Classification:


Electrical products with voltage levels ranging from 3.6kV to 550kV, used for power generation, transmission, distribution, energy conversion, and consumption in the power system to provide on/off, control, or protection functions


Product Details


Overview
SIVACON 8PT low-voltage switchgear is a new type of low-voltage switchgear designed by Siemens Company. It has circuit breaker technology, fixed installation technology and drawer type technology design. The SIVACIN 8PT produced by our company as a "licensed production partner" of Siemens is suitable for low-voltage distribution systems with AC 50HZ and rated working voltage of 690V and below. As a variety of power generation, transmission, distribution, power conversion and power consumption control equipment, can be widely used in industrial and mining enterprises, buildings, hotels, municipal construction and other low-voltage power distribution system.
The switchgear is fully in line with national standards GB7251, international standards IEC60439-I.
 
Features
The SIVACON8PT is equipped with a motor circuit and cable feed circuit drawer switch cabinet has the best safety and applicability to provide a high degree of ease of operation.
◆ Using the pull-out mechanism of the guide, it can be replaced and adjusted quickly and easily, so each module can be added or changed, even if the compartment can be changed during operation.
The use of standard modules that have passed the form test has a high level of safety. Outlet circuit can be up to 250kW. Can be protected with fuse or circuit breaker. The protection class of the test position and the separation position is IP300. All extraction units have a standard operator interface. There is an isolation gap on the supply side and the feed side. Draw-out units save space with a minimum unit height of lOOmm. The cable connection compartment can be in the front or rear, and can be easily adjusted according to changing conditions, without the need to power off the whole cabinet.
◆ The skeleton is made of 2.5mm high-quality steel plate with a hole with a modulus of 25mm. Expandable for various uses, cables can be connected above or below.
The enclosure protection grade is IP30, IP31, IP40, IP41, IP42, IP54.
◆Light weight, high mechanical strength and assembly precision, beautiful appearance.
High technical performance: the main parameters reach the international advanced level.
 
Main technical parameters
◆ Rated working voltage to 690(v)
◆ Rated insulation voltage 1000(v)
◆ Rated working current
Horizontal busbar to 7400A
Vertical bus to 2800A
◆ Rated short-time withstand current effective value (1s)/peak value (kA) to lOOkA/to 250kA
Horizontal busbar to 65kA/to 163kA
Vertical busbar to 4000A
◆ Rated current of switch
Circuit Breaker to 630A
Cable feed loop IP30 to IP54
◆ Protection grade of cabinet shell
◆ Exterior dimensions
Height: 2200mm,2600mm
Width: 400,600,800,1000,1600mm
Depth: 600,800,1000,1200mm
 
Normal use environmental conditions
◆ The ambient air temperature is not higher than 40°C and not lower than -5°C, and its average temperature is not higher than 350°C within 24 hours.
◆ Indoor installation and use, the altitude is not more than 2000 meters.
◆ Atmospheric conditions: relative humidity at maximum temperature +40. C is not more than 50%, and higher relative humidity is allowed at lower temperature, for example, 90% at +20°C, but considering the temperature change, it may cause accidental condensation.
◆ This device is suitable for transportation and storage at the following temperatures:-25°C to 55°C, up to 700°C in a short period of time (no more than 24h). Under these extreme temperatures, the device should not suffer Any irrecoverable damage, and it can work normally under normal conditions.
The equipment is installed in the place without explosion hazard, chemical corrosion and severe vibration.
◆ Beyond the above conditions of use, users have special requirements, can negotiate with the manufacturer special.
 
internal structure
The basic structure of the cabinet is composed of fixed steel plates and profiles connected to each other, which can be divided into several compartments according to needs, namely, the main bus room, the electrical room, the cable room and the horizontal wiring compartment (used to connect the control wires between the cabinet and the cabinet). The skeleton profile has a modulus M = 25mm mounting hole, and the shell is made of 2mm steel plate. Users can choose the surface treatment method (powder spraying, painting or galvanizing) according to their needs.
 

The switch cabinet has the functions of overhead incoming and outgoing lines, cable incoming and outgoing lines, bus connection, etc. Mainly suitable for power plants, substations, petrochemical, metallurgical steel rolling, light industry and textile, factories and mining enterprises and residential areas, high-rise buildings and other different places. It mainly includes high-voltage isolating switch and grounding switch, high-voltage load switch, high-voltage automatic coincidence and segmenter, high-voltage operating mechanism, high-voltage explosion-proof distribution device and high-voltage switch cabinet.

Correct Selection of Breaker Breaking Capacity
On the primary system diagram, the selected circuit breaker, indicating the circuit breaker model, rated working voltage and rated working current, must also be selected for the breaking capacity of the circuit breaker. With user drawings, the breaking capacity of the circuit breaker is not selected, which makes it difficult for the manufacturer to carry out engineering design. The breaking capacity selection should be based on the system short-circuit parameters. If the manufacturer does not understand the system short-circuit parameters, it is difficult to make the correct choice. There are also some user drawings, regardless of the system short-circuit parameters, blindly select high-break parameters, resulting in unnecessary waste of funds. The correct choice of breaking capacity is very important, not only to ensure safe operation, but also to consider reducing product costs.